Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

This FAQ describes how to set 2N® SmartCOM PRO ETH for AMS function. 2N® SmartCOM PRO can with this function automatically read data from the INPUTS and store data in the internal memory. This feature is available for all units with firmware 1.13.X

...

  • Voltage range: 0–10 V DC
  • Current range: 0–20 mA DC
  • Digital input with threshold level setting
  • S0 pulse inputs (You can increase the S0 bus resistance against interference if necessary by connecting PullUp voltage from the power supply or an internal 3V6 supply)

 

Disconnect the 2N® SmartCom PRO from the power supply before opening the cover. Be careful while handling the jumpers to avoid damaging the device destruction!


Make sure that the 2N® SmartCOM PRO ETH jumpers are set as shown in the following image

...

at^scdata="get_oldest",50
^SCDATA: "AMS",1461340261,12091,"AIN_DIN",1,0,"","131"           - results from port 1    
^SCDATA: "AMS",1461340381,12093,"AIN_DIN",1,0,"","228"           - results from port 1
^SCDATA: "AMS",1461340441,12094,"AIN_DIN",1,0,"","234"           - results from port 1
^SCDATA: "AMS",1461340681,12098,"AIN_DIN",2,0,"","21"            - results from port 2
 

Analog value on input

before measurement calibrate 2N® Calibrate 2N® SmartCOM PRO ETH inputs         inputs before measurement                               - Input circuit calibration

...

^SCDATA: "AMS",1464185221,7117,"AIN_DIN",2,0,"","848"                - output value from A/D on input 2
 

Digital value on input

before measurement calibrate 2N® Calibrate 2N® SmartCOM PRO ETH inputs         inputs before measurement                                      - Input circuit calibration

...

AT^SCAMS="DEV_ADD",128,"AIN_DIN","2/DIN","1M"                        - digital value on input 2 will be stored in memory every minute
ossiblepossible time intervals:                                              - "1M", "2M", "3M", "4M", "5M", "6M", "10M", "12M", "15M", "20M", "30M", "1H", "2H", "3H", "4H", "6H", "8H", "12H", "1D"

...