FAQ describes how to set 2N® SmartCOM PRO for AMS function by AT command. 2N® SmartCOM PRO automatically detect M-Bus meters. Then reads data from M-Bus meters and store data in internal memory. 2N® SmartCom server with web interface readout  2N® SmartCOM PRO units and parse M-Bus messages to CSV files.

 

Tested with firmware (SCE_1-12-0-12-24). Ask 2N for this firmware or  access to test web server - contact your salesman or send a request go to https://support.2n.cz

 

Connect 2N® SmartCom PRO unit to your 2N® SmartCom server. In this scenario will be used 2N® SmartCom test server with web interface.

Check, that your unit is connected to the server. (Web interface or in software 2N® Control panel)

Enable AMS function (0 = AMS turned off)

at^scams="enable",1                                                     

Meter detection:

Performing this command deletes all the data from 2N®SmartCom PRO terminal memory as well as the meter reading configuration part. The parameter interval is global for all installed meters by AT command.

AT command:
at^scamsadd=<port>,<protocol>,<baudrate>,<interval>,<number_of_expected_devices>

Examples: 

(detection 2 meters on M-Bus, for speed 2400 Bd and interval 1 minute)

at^scamsadd=2,2,"default","1m",2

at^scamsadd=2,2,2400,"1m",2

at^scamsadd=2,"mbus","default","1m",2

at^scamsadd=2,"mbus",2400,"1m",2

possible interval for data reading from meters - values: 1M, 2M, 3M, 4M, 5M, 6M, 10M, 12M, 15M, 20M, 30M, 1H, 2H, 3H, 4H, 6H, 8H, 12H, 1D

 

Answer:
^SCAMSADD: <error_code>,<number_of_devices>,"<primary_address_1>,<secondary_address_1>;<primary_address_2>,<secondary_address_2>;................."
OK

 

Examples:

without error - 2 meters found

^SCAMSADD: 0,2,"0,08031768;1,15020416"

error - different number of meters found (only 1)

^SCAMSADD: 65286,1,"0,08031768"

error(collision of secondary addresses)

^SCAMSADD: 131094,0,""

 

 

Go to web interface to section "Terminals Monitoring" and synchronize your 2N® SmartCom PRO unit with 2N® SmartCom server.

 

Press Start sync

 

 

Wait until synchronization is finished

 

 

In section "Meters" you can find information about your M-Bus meters

 

 

Results are in section - "Results" - For the access data (login, password) please contact your salesman or send a request go to https://support.2n.cz

 

or can be download by FTP client - loggin name: ask 2N

 


General AMS errors
0                  - without error 
1                  - error of input data 
2                  - error of output data 
3                  - protocol cannot be used for this port
4                  - readout not started

M-Bus AMS errors
131072                 - non specific error (internal error of module)
131073                 - readout was stopped by user
131074                 - bad format address and speed of the device
131075                 - parameters of the port were not set
131076                 - message "SND_NKE" was not send in defined time interval to the device
131077                 - message "SND_NKE" was not send in defined time interval to the device
131078                 - timeout - receiving "SND_NKE" message response
131079                 - bad frame when receiving "SND_NKE" message from the device
131080                 - message "REQ_UD2" was not send
131081                 - message "REQ_UD2" was not send
131082                 - timeout - receiving "REQ_UD2" message response
131083                 - incorrect communication frame for "REQ_UD2" message
131084                 - incorrect response for "REQ_UD2" message
131085                 - incorrect device address in response for "REQ_UD2" message
131086                 - message "SND_UD slave selection" was not send in defined time interval
131087                 - message "SND_UD slave selection" was not send in defined time interval
131088                 - timeout - receiving "SND_UD slave selection" message response
131089                 - bad frame for "SND_UD slave selection" response message
131090                 - message "SND_UD slave selection" was not send in defined time interval during searching slaves on bus
131091                 - message "SND_UD slave selection" was not send in defined time interval during searching slaves on bus
131092                 - message "REQ_UD2" was not send in defined time interval during searching slaves on bus
131093                 - message "REQ_UD2" was not send in defined time interval during searching slaves on bus
131094                 - collision of secondary addresses during searching slaves on bus (two or more devices have same secondary address)
131329                 - bad first "start" byte for device´s response message
131330                 - bad second "start" byte for device´s response message
131331                 - bad first "stop" byte for device´s response message
131332                 - bad checksum of the response frame
131333                 - bad value of the response frame length
131334                 - bad value of the response frame length